Description
Para 25-130/8-75/SCU-12 Circulation Pump
Product Details
| Feature | Specification |
|---|---|
| Model | Para 25-130/8-75/SCU-12 |
| Type | Electronically controlled glandless circulation pump |
| Pump Housing | Cast iron (cataphoresis-treated) or composite |
| Connection (Inlet/Outlet) | G 1½ |
| Port-to-Port Length | 130 mm |
| Dimensions (L1 × L2 × L3) | 105 mm × 138 mm × 65 mm |
| Gross Weight | 1.8 kg (approx.) |
| Voltage / Frequency | 1~230V (+10% / -15%), 50/60 Hz |
| Power Consumption | 4 W (min) – 75 W (max) |
| Standby Power | ≤ 0.5 W |
| Max Current | 0.66 A |
| Maximum Operating Pressure | 10 bar |
| Temperature Range | -10°C to +95°C (fluid); -10°C to +70°C (ambient) |
| Approved Liquids | Heating water (VDI 2035), Water-glycol (max 1:1; check data above 20% glycol) |
| Minimum Suction Head | 0.5 m (at 50°C), 4.5 m (at 95°C) |
| Energy Efficiency Index | ≤ 0.21 |
| Protection Class | IPX4D |
| Insulation Class | F |
| Motor Protection | Integrated |
| Approvals | CE / EAC / UA |
| Impeller Material | PP-GF40 (Polypropylene, 40% glass fiber) |
| Shaft Material | Stainless steel |
| Bearing Material | Carbon |
| Special Features | LED interface, preset modes, automatic power adjustment, manual restart, air venting, 3-way connector (PR60-61), compact design, easy installation |
Technical Features
- Self-deblocking Function – Prevents motor lock-up during inactivity
- Anti-rust Rotor Technology – Prevents shaft corrosion during long downtimes
- Air Venting Mode – Removes trapped air automatically during startup
- Thermal Overload Protection – Protects motor from overheating
- Dry-Run Resistant Bearings – High-grade carbon bearings prevent damage during dry starts
- Automatic Speed Adaptation – Matches system demand via Δp-v / Δp-c logic
- Manual Restart Button – Easy reset after fault or long shutdown
- Power Surge Protection – Handles voltage fluctuation up to ±15%
- Tool-Free Wiring Access – Quick electrical connection via front terminal
- Compact Inline Design – Space-saving for tight OEM enclosures
- Silent EC Motor – Noise level optimized for residential use
- Low Minimum Suction Head – 0.5 m at 50 °C (prevents cavitation)












Reviews