Description
Electrical Specifications
(380 V, 3-phase, star configuration, balanced resistive load, power factor ≈ 1)
- Voltage: 380 V (3~)
- Frequency: 50/60 Hz
- Factory wiring: Star (Y)
- Control: 3 independent circuits (6 leads) for staged/stepped control
Model-specific data:
|
Model |
Power |
Line Current |
Power per Element |
Resistance (Star) |
Resistance (Delta, ref.) |
|
FIH-380/6 |
6 kW |
≈ 9.12 A |
2.0 kW |
24.07 Ω |
72.20 Ω |
|
FIH-380/9 |
9 kW |
≈ 13.67 A |
3.0 kW |
16.04 Ω |
48.13 Ω |
|
FIH-380/12 |
12 kW |
≈ 18.23 A |
4.0 kW |
12.03 Ω |
36.10 Ω |
|
FIH-380/15 |
15 kW |
≈ 22.79 A |
5.0 kW |
9.63 Ω |
28.88 Ω |
Note: Delta connection values are for reference only. Units are factory-configured for 380 V in star (Y) configuration. Using delta at 380 V will triple the kW and is not allowed unRecommended protection devices (to be confirmed per cable/ambient/code):
- 6 kW → 3P 16 A
- 9 kW → 3P 20 A
- 12 kW → 3P 25 A
- 15 kW → 3P 32 A
Mechanical & Material Specifications
- Sheath Material: Incoloy 800 (water heating grade)
- Tube Diameter (OD): Ø8.5 mm (Ø11 mm heavy-duty optional)
- Insulation: High-purity compacted magnesium oxide (MgO)
- Mounting Plate: Stainless steel, square/rectangular, gasketed; mounting pattern as per order (e.g., P90×90, 4×M6)
- Connections: Six high-temp lead wires with strain relief, and a grounding lug on the plate
- Cold Zone: A defined non-heated section from the mounting plate to the beginning of the heated length
- Ingress Rating: Depends on terminal housing; open-lead assemblies are not IP rated. Add a terminal head for IP54 to IP65 protection
Watt Density & Recommended Lengths (for water heating)
- Standard Watt Density Target: ~8 W/cm²
- Low Watt Density Option (for hard water or continuous high temp): ≤ 4–6 W/cm²
- Indicative Minimum Immersion Length per Leg (Ø8.5 mm at 8 W/cm²):
- 6 kW ≈ 0.47 m
- 9 kW ≈ 0.70 m
- 12 kW ≈ 0.94 m
- 15 kW ≈ 1.17 m
Recommended Accessories & Controls
- Thermostat pocket or NTC sensor sleeve
- Manual reset high-limit thermal cut-out
- Terminal head (IP54–IP65) with cable gland set
- RCD/ELCB protection and 3-pole MCB/contactor (as per rating)
- Anode strategy (if installed in storage tanks)
Installation & Safety Guidelines
- The heating portion must be fully submerged during operation – never operate dry
- Mount vertically where possible to avoid air pockets at the tip of the element
- Use proper gasket and torque; ground the plate securely
- Include flow or level interlocks; plan for periodic descaling in hard water areas